ST9000 | Multi-speed function – Simple frequency or change of rotating direction
Multi-speed Function:
Speed1=50Hz, Speed2=40Hz and Speed3=30Hz
F0.03 = 6 | frequency control on multi-speed |
F0.11 = 1 | regulator release on terminal clamps |
F0.13 = 4 | Acceleration time 4 sec. |
F0.14 = 4 | Deceleration time 4sec |
F1.00 = 1 | DI1 terminal for the Run command |
F1.04 = 12 | DI5 selection for multi-speed |
F1.05 = 13 | DI6 selection for multi-speed |
E1.00 = 100 | 100% of the target frequency F0.19 |
E1.01 = 80 | 80% of target frequency F0.19 |
E1.02 = 60 | 60% of target frequency F0.19 |
After regulator release to DI1 the drive at the target frequency runs off with a braking and acceleration time of 4sec.
If there is a release via DI5 to DI1, the inverter will run with 40Hz.
A release via DI6 and DI1, causes a frequency of 30Hz.
Tags: