ST9000 | Braking and acceleration times
With ST9000 frequency inverter it is possible to retrieve various functions via the terminals DI1 to DI8. One of them is to select different braking and acceleration times during operation.
You may define 4 different braking and acceleration times and select these by using the DI terminals. Here is a configuration of two other times when terminals were chosen DI5 and DI6.
F0.11 = 4 | Operation via terminal clamps and panel |
F1.04 = 16 | Terminal DI5 for Ac / Dc Terminal1 |
F1.05 = 17 | Terminal DI6 for Ac / Dc Terminal2 |
F0.13 = 10 | Acceleration time T1 to 10 sec |
F0.14 = 10 | Braking time T1 to 10 sec |
F7.08 = 5 | Acceleration time T2 to 5sec |
F7.09 = 5 | Deceleration time T2 to 5sec |
F7.10 = 1 | Acceleration time T3 1sec |
F7.11 = 1 | Braking time T3 1sec |
If no level signal is applied to the terminals DI5, and DI6, the T1 time is used.