ST600s | Frequency converter as pump control – Parameter list for pressure control

Note: Unchanged factory settings (except motor parameters) are assumed.

Programmed values:

Parameter Value Functional description
P00.01 1 Terminal control active
P00.06 7 Main frequency control source = PID
P00.11 10 Acceleration time in seconds – adjust during commissioning if necessary
P00.12 10 Braking time in seconds – adjust during commissioning if necessary
P00.13 2 Reverse operation blocked
P01.18 1 Start-up protection deactivated
P04.00 4 V/f characteristic curve quadratic
P05.01 1 S1 = Forward command
P05.24 2 Minimum voltage at AI1 = 2V (corresponds to 4mA)
P05.50 1 AI1 = current input
P09.00 0 PID setpoint source = P09.01
P09.01   PID setpoint (setting range: -100% to +100%)
P09.02 0 PID feedback source = AI1
P09.08 0 PID Deviation limit
Menu Uploading the set parameters to control panel memory location 2

Italics: Factory setting, listed for illustrative

Motorparameter:

Parameter Value Functional description
P02.01 Nominal engine power in kW
P02.02 Nominal motor frequency in Hz
P02.03 Nominal motor speed in rpm
P02.04 Nominal motor voltage in V
P02.05 Rated motor current in A

For a detailed explanation of the individual functions of the parameters, please consult the manual.

Pin assignment:

Sourcetronic
ST600
Functional description
R Mains to supply or main switch
S
T
PE
U Motor directly at the FI
V
W
PE
+24V Together with COM voltage source e.g. for signal light (max. 200mA minus sensor)
COM Reference potential of the +24V source
PW This is the opposite pole to the potential on an active input terminal.

In factory setting connected to COM, so that a terminal is active when it is

is connected to +24V

S1 On: Start forward with ramp P00.11; Off: Brake with ramp P00.12
AI1 Analogue input 1 (4-20mA)
+10V Analogue auxiliary voltage
GND Analogue reference potential
RO1A, RO1B, RO1C Relay output 1 = Inverter in operation
RO2A, RO2B, RO2C Relay output 2 = Error signalling

 

Commissioning

The connections R, S, T of the frequency inverter are connected to the mains directly behind the main switch, the motor in the star to the connections U, V, W of the inverter.

The pressure sensor is connected as follows:

+Ub to terminal +24V

GND to terminal AI1

In addition, a jumper from COM to GND must be set on the inverter.

The start switch is connected between S1 and +24V of the inverter. As soon as the start switch is closed or the start button on the control panel is pressed, the inverter starts PID control. If the start switch is opened or the stop button on the control panel is pressed, the inverter stops.

Relay 1 of the inverter (RO1C/RO1A) can be used to control an operating light, for example. If the internal 24V source is used for this, the lamp and pressure sensor together must not draw more than 200mA.

Relay 2 switches from RO2B/RO2C to RO2A/RO2C in case of a fault.