ST600s | Err.33, what does this message mean, what can be done?

If the error message Err.33 appears on the display of the frequency inverter, it is the ground fault 2.

Causes:

  • The output of the frequency inverter is connected to ground.
  • Error in the current detection circuit.
  • The actual motor power differs greatly from the VFD power.

Solutions:

  • Check that the motor wiring is correct.
  • Replace Hall sensor.
  • Replace the main control board.
  • Reset the motor parameters as instructed.

If none of these error sources apply, please contact technical support.

Tags: