ST600s | Err.07, what does this message mean, what can be done?
If the display of the frequency inverter shows the error message Err.07 appears, it is overvoltage during acceleration.
Causes:
- A fault has occurred in the input voltage.
 - Strong energy feedback.
 - Missing brake units.
 - The dynamic brake is not activated.
 
Solutions:
- Check the input power.
 - Check whether the acceleration time P00.11 is too short or whether the motor starts when turning.
 - Build in dynamic braking units.
 - Check the setting of the corresponding function codes P08.37 and P08.38.
 
If none of these error sources apply, please contact technical support.