ST500 | Frequency converter as pump control – Parameter list for pressure control

Note: Unchanged factory settings (except motor parameters) are assumed.

Programmed values

Parameter Value Functional description
F0.03 8 PID control
F0.11 4 4: All control sources (control panel, control terminals, interface)
F0.13 10 Acceleration time 1 – adjust during commissioning if necessary
F0.14 10 Braking time 1 – adjust during commissioning if necessary
F1.16 2 Minimum voltage at AI2: 2V corresponds to 4mA corresponds to 0%.
F1.42 1,00 Setting range of the rotary encoder 100 steps from 0 to 100%.

or from 0.0bar to 10.0bar

F1.44 0,00 Minimum value control panel rotary encoder
F1.45 100,00 Maximum value control panel rotary encoder
F6.16 d0.16 Lower display line:

d0.09 Voltage at AI1 after correction by F1.16-F1.19

d0.16 PID feedback variable scaled with E2.04

F7.17 1 Reverse operation blocked
F7.46 20 Inverter only wakes up again when the PID controller would run the pump at >20Hz
F7.47 0 Waiting time for F7.46
F7.48 15 Inverter goes into sleep mode if the PID controller wants to run the pump at <15Hz for longer than F7.49
F7.49 2 Waiting time for 7.48
FC.02 5 Start deviation 5% from setpoint
E2.00 3 PID setpoint: Control panel rotary encoder
E2.02 1 Feedback variable: analogue signal 4..20mA at AI2
E2.04 10 Scaling for the display in d0.16: At 100% this value is displayed, corresponding to 10bar
E2.06 2 PID deviation limit
E2.27 1 Continue PID calculation in stopped state
Y0.00 12 Upload the previously set parameters to control panel memory location 2 for later restoration (see below).

 

Italics: Factory setting, listed for illustrative purposes only

 

Motor parameters

Parameter Value 4kW Functional description
B0.01 Nominal engine power in kW
B0.02 Nominal motor voltage in V
B0.03 Rated motor current in A
B0.04 Nominal motor frequency in Hz
B0.05 Nominal engine speed in rpm – for display purposes only

For V/f control, entering the motor parameters is not mandatory, but is recommended to enable the inverter’s motor protection functions.

 

In case of problems

Parameter Value Functional description
Y0.00 22 Downloading the set parameters from control panel memory location 2

For a detailed explanation of the individual function of the parameters, please consult the manual.

 

Terminal assignment

Sourcetronic
ST500
Functional description
R Mains to supply or main switch
S
T
PE
U Motor directly at the FI
V
W
PE
+24V Together with COM voltage source e.g. for signal lamp (max. 200mA minus sensor).

The +Ub connection of the pressure sensor is connected here.

COM Common contact digital inputs DI1-DI8
DI1 On: Start forward with ramp F0.13 in control mode; Off: Brake with ramp F0.14
GND Must be bridged with COM so that the 24V source can be used for the sensor at the (normally potential-separated) analogue input
AI2 The GND connection of the pressure sensor is connected here.
TC1 Relay 1: TC1 – TA1 closed if an error has occurred.

Otherwise TC1 – TB1 closed

TA1
TB1
TC2 Relay 2: TC2-TA2 closed when FI in operation

Connection option for e.g. operating lamp

TA2

 

Commissioning

The connections R, S, T of the frequency inverter are connected to the mains directly behind the main switch, the motor in the star to the connections U, V, W of the inverter.

The pressure sensor is connected as follows:
+Ub to terminal 24V
GND to terminal AI2
In addition, a jumper from COM to GND must be set on the inverter.

The rotary encoder has a basic resolution of 0.01% per step (without acceleration setting in). In the setting F1.42=1.00 there are exactly 100 steps from 0 to 100%. The factory setting of 0.50 would be 50 steps. With parameters F1.44 and F1.45, the value range can be limited if necessary, e.g. with F1.44=40.00 and F1.45=65.00 to 40-65% corresponding to 4.0 to 6.5bar, still in the same number of steps.

The start switch is connected between DI1 and COM of the inverter. As soon as the start switch is closed or the start button on the control panel is pressed, the inverter starts PID control. When the start switch is opened or the stop button on the control panel is pressed, the inverter stops.

Relay 1 switches from TB1/TC1 to TA1/TC1 in the event of a fault.

Relay 2 of the inverter (TC2/TA2) can be used to control an operating light, for example. If the internal 24V source is used for this, the lamp and pressure sensor together must not draw more than 200mA.

If the target frequency falls below 15Hz for more than 2 seconds, the inverter goes to sleep. If the target frequency exceeds 20Hz and the deviation from the target value is greater than 5%, the inverter continues operation. Depending on the dynamics of the piping system, it may be necessary to adjust the setting values for FC.02, E2.06 and F7.46-49.

If the pump has specified a minimum frequency, this should be used for F7.48 and F7.46 should be adjusted accordingly.