ST500 | Parameter transmission to the control unit – What do I have to do?

To transfer all parameters stored in the frequency inverter to the memory location of the control unit, proceed as follows:

  1. Go to parameter y0.00 and select 11 or 12. Now all function parameters including motor parameters are transferred to the control unit memory location 1 or 2.
  2. To transfer parameters from the control unit memory location 1 or 2 to the inverter, the parameter y0.00 = 21 or 22 must be executed.

Caution: Correct transfer between different hardware revisions cannot be guaranteed. For example, the C3 version keypad is not compatible with the C4 version inverter.

In addition, the transfer of a frequency inverter of the ST9000 series to the ST500 series is only possible through software and not through the control unit alone.

Back to the frequency inverter ST500 questions.

Tags: