ST130 | Initial commissioning – What do I have to observe (motor data)?

Before commissioning a frequency inverter, it is essential that the factory settings are loaded y0.00 = 1.

Then the rated motor data of the motor used are programmed into the inverter. These can be found on the rating plate of your motor.

Example of a nameplate belonging to a three-phase asynchronous motor

Figure: Type plate

The required parameters are located in the -b- parameter group. These are the parameters b0.00 to b0.11.

  • Nominal voltage (b0.02): 230V (delta connection) / 400V (star connection)
  • Nominal frequency (b0.04): 50Hz (for frequencies above 50Hz, adjust F0.08 and F0.10 first)
  • Nominal current (b0.03): 3.98A (delta connection) / 2.30A (star connection)
  • Nominal speed (b0.05): 1385 rpm
  • Rated power (b0.01): 0.75kW
  • All other parameters can also be measured by the inverter itself. b0.11 = 2 for rotating measurement without load or b0.11 = 1 for stationary measurement if the load cannot be disconnected. If possible, always carry out a rotating measurement without load, this leads to more accurate values.