ST130 | Forward, Reverse, Stop – Which parameters and terminal assignment?
The ST130 frequency inverters have terminals DI1, DI2 and DI3 with which the inverters can be switched to forward and reverse operation via control pulses or simple pushbuttons. In order for the inverters to accept the control pulses from the terminals, F0.04 = 1 must first be set.
Terminal assignment and parameterization in detail:
F0.04 = 1 | (control mode on terminals/terminals) |
F1.00 = 1 | (Digital input DI1 – Forward control command) |
F1.01 = 2 | (Digital input DI2 – reverse control command) |
F1.02 = 8 | (Digital input DI3 – Control command free stop) |
The buttons for switching must be connected between terminals DIx and COM.