ST130 | For an emergency stop button I need a free stop – What do I have to do?

The ST130 frequency inverter has the terminals DI1, DI2 and DI3 with which the inverter can be switched to a free stop via control pulses or simple buttons. In order for the inverter to accept the control pulses from the terminals, F0.04 = 1 must first be set.

Terminal assignment and parameterization in detail: Switch e.g. on DI1

F0.04 = 1 (control mode on terminals)
F1.02 = 8 (Digital input DI3 – Free stop control command)
F3.05 = 1 (for free stop), F3.05 = 0 (braked stop)
F1.19=001 Invert polarity of port DI1