ST130 | Digital inputs – What can be connected and how?
The digital inputs of the ST130 enable the inverter to be controlled by means of sensors, switches, a PLC etc. The terminals DI1 to DI5 are used for connection.
For each of these 5 terminals, up to 24 different functions can be parameterized, which are triggered by a control pulse at the input.
The sensor or switch is connected between the respective input terminal and COM.
The functions must be parameterized for the following parameters:
Terminal |
Parameter |
Description |
DI1 |
F1.00 |
Digital input |
DI2 |
F1.01 |
Digital input |
DI3 |
F1.02 |
Digital input |
DI4 |
F1.03 |
Digital input |
DI5 |
F1.04 |
Digital input |
Whether the digital inputs should react to either high or low levels can be set in parameter F1.19.
F0.04 = 1 for control only via terminals